X Series375 and 500 Watt AC-DC Converters

Input range 85...264 V AC with PFC1 or 2 isolated, regulated outputs up to 96 V3 kV AC I/O electric strength test voltageLGA•Electrically and mechanically rugged DIN-railfront end

•Outputs individually controlled with 150%output peak power

•Operating ambient temperature range–40...60°C with convection cooling

Selection chart for front endsOutput 1Uo nomIo nom[V DC][A]24.71524.720379.93713.249.47.549.41024.71049.45Output 2Uo nomIo nom[V DC][A]------------24.71049.45Input voltageUi min…Ui maxRated powerTA = 60°CPo tot [W]375500375500375500500500TypeOptions185…264 VAC(14…440 Hz)390…350 VDCLXR 1601-6LXN-1601-6LXR 1701-6LXN 1701-6LXR-1801-6LXN-1801-6LXN-2660-6LXN 2880-6RD1…D5SM2F, F1 K2Selection chart for Battery chargers2Rated powerTypeOptions1Uo nomIo nomTA = 60°C[V DC][A]Po tot [W]25.7...29.312.685…264 VAC345LXR 1240-6 M1F, F125.7...29.316.9460LXN 1240-6 M1K2(14…440 Hz)351.4...58.66.390…350 VDC345LXR 1740-6 M151.4...58.68.4460LXN 1740-6 M11 For lead times and minimum order quantities contact Power-One.2 For availability contact Power-One.

3 Input frequency range certified for 14...440 Hz. For continuous operating frequency <40 Hz and >100 Hz contactfactory.

OutputInput voltageUi min…Ui maxwww.power-one.com

Edition 5/7.2001

1

元器件交易网www.cecb2b.com

X Series

Input

Input voltageInput frequencyPower factorInrush current375 and 500 Watt AC-DC Converters

world wide mains, single phase

for derating information see application notewide frequency rangeactive PFCvirtually no inrush current85...264 V AC90...350 V DC16 2/3...440 Hz

up to 0.99Output

EfficiencyOutput voltage setting accuracyOutput voltage noiseOutput voltage rippleLine and cross regulationLoad regulationMinimum loadCurrent limitation

Short term peak powerOperation in parallelHold-up timeUi nom, Io nomup to 89%Ui nom, Io nom±1.3% Uo nomIEC/EN 61204typ. 50 mVsinusoidal output ripple at twice the line frequency ≤1.2 VppUi min...Ui maxtyp. 50 mV0...100% Io nom, Ui nom–1.6% Uo nomnot requiredrectangular U/I characteristic101...112% Io nom1 s, electronically controlled150% Io nomenabled by droop current share

Io nom, Uo decreases to 80% of Uo nomtyp. 15 msControl

Status indicationLED output(s) OKProtection

Input reverse polarity

Input fuseInput undervoltage lockoutInput overvoltage lockoutInput transientOutput(s)Output overvoltageOvertemperaturebridge rectifier

not user accessible10 A, fast blowtyp. 80% Ui mintyp. 105% Ui max

voltage depending resistor (VDR)

no-load, overload and short circuit proofsecond control loop, each output, 24/48 Vreduced output power if thermally overloaded 30/60 V SELV

Safety

Approvals in progressElectric strength test voltage

EN 60950, UL 1950, CSA22.2 No. 950, UL 508 listedclass I, I/caseclass I, I/Oclass I, O/caseclass I, O/OAC-in / DC-in

2 kV AC3 kV AC 1 kV AC 0.35 kV AC3/2IP 20Pollution degreeDegree of protectionwww.power-one.com

Edition 5/7.2001

2

元器件交易网www.cecb2b.com

DIN Rail Mountable

EMC

Electrostatic dischargeElectromagnetic field

Electr. fast transients/burstsSurge

IEC/EN 61000-4-2,IEC/EN 61000-4-3,IEC/EN 61000-4-4,IEC/EN 61000-4-5,

X Series

level 4, contact/air (8/15 kV)criterion Alevel 3 (10 V/m)criterion Alevel 4, capacitive/direct (4/2 kV)criterion Alevel 3, in and out, line to line (2 kV)criterion Blevel >3, input, line to case (3.5 kV)criterion Blevel 2, output, line to case (1 kV)criterion A

IEC/EN 61000-4-6,level 3 (10 V)criterion ACISPR 22/EN 55022, conductedclass B

Conducted disturbancesElectromagnetic emissions

Environmental

Operating ambient temperatureOperating case temperature TCStorage temperatureDamp heat

Shock and vibrationShockBumpVibration, sinusoidalVibration, randomMTBF

Ui nom, Io nom, convection cooledUi nom, Io nom

non operationalIEC/EN 60068-2-3, 93%, 40°Cunit wall mounted with bracketsIEC/EN 60068-2-27, 11 msIEC/EN 60068-2-29, 11 msIEC/EN 60068-2-6, 10...60/60...2000 HzIEC/EN 60068-2-64, 20...500 HzMIL-HDBK-217E, GB, 40°C

–40...60°C–40...87°C–40...100°C56 days50 gn25 gn

0.35 mm/5 gn

0.05 g2/Hz400'000 h

Options

Input and output undervoltage monitoringOutput voltage adjustment10 V...110% of Uo nomRemote on/off

Multi option choice(D1...D5, R, S) via Sub-D connectorBuilt-in second input fuse in the neutralNo fuse fittet (for operation from high DC)System connectors with screw terminals

D1...D5

RSM1...M2FF1K2

www.power-one.com

Edition 5/7.2001

3

元器件交易网www.cecb2b.com

X Series

Mechanical data

375 and 500 Watt AC-DC Converters

EuropeanProjectionTolerances ±0.3 mm (0.012\") unless otherwise indicated.

15 (0.59\")204 (8.03\")()196 (7.71\")()194 (7.64\")()29.4 (1.16\")113.6 (4.47\")106.6 (4.2\")S09127138 (5.43\")Option M13 (0.51\")31 (1.22\")TAWall mountingbrackets(accessory)TAMeasuring point forcase temperatureTC43 (1.69\")www.power-one.com

Edition 5/7.2001

4

49 (1.93\")33 (1.3\")元器件交易网www.cecb2b.com

DIN Rail Mountable

X Series

Terminal allocation input side

S10066PinDes.Determination1Protective earth2NInput neutral3PI123Terminal allocation output side

S90048PinDes.Single outputDouble output1Earth to loadEarth to load2+Output pos.Output 1 pos.1234567891011123+Output pos.Output 1 pos.4–Output neg.Output 1 neg.5–Output neg.Output 1 neg.6+Output pos.Output 2 pos.7+Output pos.Output 2 pos.8–Output neg.Output 2 neg.9–Output neg.Output 2 neg.10Aux1OptionsOptions11Aux2OptionsOptions12Earth to loadEarth to loadAccessories

Mounting brackets for vertical chassis/wall mountingProtective covers over input and output terminals

www.power-one.com

Edition 5/7.2001

n