一、 无源无线温度传感器安装 ······················································································· 2 二、 无源无线温度读取天线安装 ··················································································· 3 三、 无源无线温度读取器安装 ······················································································· 4 四、测温主控终端安装 ··········································································································· 5 五、温度监测应用系统安装 ··································································································· 6 附录 ·················································································································································· 7 安装记录表······································································································································· 7 WTS-SG-1无源无线温度监测系统传感器位置配置表 ·································································· 8 主控终端安装表 ······························································································································· 8
工程实施流程图及分工界面 ··································································································· 9
江 苏 声 立 传 感 技 术 有 限 公 司
第一部分 安装须知
1. 在安装系统之前应收集变电站相应高压开关柜的技术资料、安装位置以及上级系统的技术资料,充分的进行设计及论证,同局方协商,制定详细的安装方案。
2. 安装人员作业前应学习有关安全生产知识,规章制度及安全技术操作规程,增强安全意识,提高安全生产技能,在施工中严格执行电力建设安全施工管理的有关规定,认真采取防护措施,严防事故,在保证工程顺利进行的同时达到相关技术要求。
3. 进场前,准备好所用全部需用的工具、设备,工程所需的全部材料,高压室内需用的连接线需事先做好线头,尽量缩短在高压室的施工时间。
4. 当在开关柜安装温度传感器,一定要遵照与局方协商的安装方案,注意人身及设备安全。
5. 各设备的安装位置一定要考虑周全,特别是在高压开关柜部分,传感器的安装一定要做到不漏检。
6. 温度监测终端安装时,一定要确定好在机柜的位置,确定开孔尺寸,调整好本装置的参数设置。
7. 安装完毕后,要留心考查,不要留下任何隐患,若发现有漏检的情况,一定要立即排查。必须做到检测准确,设备位置标示清楚,无系统漏检情况。
8. 安装过程中及结束后,要对局方进行详细的操作及安装、维护等知识的培训。 9. 在安装中,每位员工务必要作好施工日志(记)、技术交底、通讯线缆的走向示意图及测温系统与开关柜编号对应表、设备安装地点的布置图.在安装完成后统一交回公司。
1
江 苏 声 立 传 感 技 术 有 限 公 司
第二部分 系统安装规程
一、 无源无线温度传感器安装
传感器安装之前应先确定安装位置以及导电排相号与传感器编号对应关系并登记在《安装记录表》中,安装位置若是无法利用设备自身螺栓固定则考虑用耐高温双面胶粘接。
1. 传感器呈圆柱状,下面有U形固定片,可通过设备自身的螺栓将传感器平整的嵌入到开关柜进出线的母排上,使传感器的固定片与开关柜母排触点的金属面结合紧密,如图1所示:
图1 传感器安装位置
2. 安装时应尽量使传感器与传感器之间相互的间隔满足在20cm以上,如图2所示:
图2 传感器安装示例
3. 传感器的天线尽量远离片状金属物体,与其内壁金属物体的距离大于10cm,如图3所示:
2
江 苏 声 立 传 感 技 术 有 限 公 司
图3 传感器安装示例
4. 传感器安装完成后应再次确定传感器编号与相线编号对应。
二、 无源无线温度读取天线安装
1.温度读取器的天线可吸附于开关柜腔体内侧壁上,能覆盖到相对应传感器的位置,保证天线与所覆盖的传感器天线平行,并与导电排之间距离大于10cm或者规定的安全距离,如图4所示:
图4 温度读取天线安装位置实例
2. 温度读取器的天线亦可吸附于开关柜腔体内的中部,在保证安全间距前提下尽量靠近所覆盖的传感器,可通过调整读取天线方位使得与传感器天线尽量保持平行,如图5所示:
3
江 苏 声 立 传 感 技 术 有 限 公 司
图5 温度读取天线安装实例
3.温度读取天线位置固定后布置射频线走线,可通过设备本身线槽布线,为减少线缆损耗尽可能缩短走线长度,并将多余的线缆用扎带捆绑。
三、 无源无线温度读取器安装
1. 温度读取器背面有卡槽,可安装在开关柜配电盘部分的导轨上,如图6所示;
图6 温度读取器安装位置实例
2.温度读取器天线射频端口连接温度读取天线,温度读取天线从开关柜侧壁通过合适的走线引至对应的温度读取器天线射频口上。
3.温度读取器采用RS485总线与温度监测终端连接,485总线平整铺设在线槽内,选择合适的走线路径,使之到测温主控终端的距离最短。485总线使用线径≥0.3平方毫米的屏蔽两芯铜双绞电缆,距离必须小于100M,屏蔽层都必须接地。
4.若选择电源适配器对温度读取器供电,则需在配电盘中布置AC220V两孔插座,通过电源适配器将5V直流电接入温度读取器电源输入口。
4
江 苏 声 立 传 感 技 术 有 限 公 司
四、测温主控终端安装
1.单机版测温主控终端
可根据其开孔尺寸安装在开关柜仪表室柜门(或开关柜便于巡检的地方),使用交流220v供电。该终端与温度读取器通过RS485线连接进行数据传输,并同时向温度读取器提供5V电源。当一个开关柜的无源无线传感系统安装完成后,使用单机版测温主控终端进行参数设置、温度校准、系统功能及安装验证。单机版测温主控终端的使用方法见《WTS-SG-1型无源无线温度传感系统用户手册》。
图7 单机版测温主控终端安装实例
2.网络版测温主控终端
工业平板计算机,安装在监控机房的标准机柜内(或根据用户要求进行安装),使用交流220v供电。该终端通过RS485总线连接多个温度读取器。当多个开关柜的无源无线传感系统完成后,应使用网络板测温主控终端对所有被测设备进行参数设置、温度校准、系统功能及安装验证。网络版测温主控终端的使用方法见《WTS-SG-1型无源无线温度传感系统用户手册》。
图8 网络版监控终端安装实例
5
江 苏 声 立 传 感 技 术 有 限 公 司
五、温度监测应用系统安装
1.可根据局方要求,使用变电站自动化系统的监测功能,我方通过RS485接口总线按指定的规约进行连接,在原变电站自动化系统的监测系统进行配置,配置完成后,经检验无误后,进行系统联调,联调完成后,就可实现对开关柜温度的监测及告警等功能,系统安装完毕,即可进入系统试运行,安装阶段完成。
2.当后台处理采用我公司的开关柜温度监测主控终端时,需另行购置单机版显示仪表或工业计算机等监控终端设备,网络版还需安装本公司提供的网络版温度监测系统应用软件,由它完成单个开关柜或多个监测点的温度信息及温度告警信息的处理。主控终端仍以RS485总线接口同温度读取器进行通信。当各项硬件设备完成安装后,通过主控终端系统进行各项参数配置,配置完成后,经检验无误后,进行系统联调,联调完成后,就可实现对开关柜温度的监测及告警等功能,系统安装完毕,即可进入系统试运行,安装阶段完成。
6
江 苏 声 立 传 感 技 术 有 限 公 司
附录 安装记录表
安装用户 联系人 站址 站型 主站监控系统 电话 厂家: 接口方式: 接口规约: 温度监控方式 单机版监控 □ 网络版监控 □ 自动化监测系统 □ 监控终端提供方式 温度告警值 开关柜序号 (可续) 厂家型号 本公司 □ 外司 □ 提供类别 高温预警值: 低温预警值: 测温点1 测温点2 测温点3 测温点4 测温点5 测温点6 7
江 苏 声 立 传 感 技 术 有 限 公 司
WTS-SG-1无源无线温度监测系统传感器位置配置表
序号 开关柜运行编号 *说明: 安装点1 安装点2 安装点3 安装点4 安装点5 安装点6 读取器地址 安装时间 根据实际安装的传感器位置填写上表 例如:
运行编号:10KV普环三线905开关
安装点1:真空断路器上部与隔离开关连接处A相进线端
主控终端安装表
主控终端类别 1 2 3 安装位置 连接RS485口所在位置 220V电源连接位置 开关柜运行编号
8
江 苏 声 立 传 感 技 术 有 限 公 司
工程实施流程图及分工界面
确定需安装测温的开关柜 制定安装方案 设备及材料、工具到场 工程实施 1、开关柜内安装实施、校准测试,同时在监控机房进行控制终端安装调试 2、从读取器到控制终端布线 3、参数设定、系统联调 系统验收 局方负责 施工方负责、局方审核 局方确定具体安装时间(停电计划) 施工方负责 施工方负责、需要局方系统配合 施工方、局方 9